The discharge current is the most important parameter for selecting a surge protector, which symbolizes the ability of the surge protector to discharge lightning current and protect equipment. When defining the discharge current parameters of the surge protection device, the discharge current is divided into the nominal discharge current and the maximum discharge current.
In the relevant standards, for the pressure-limiting lightning arrester, use the lightning arrester to allow the maximum discharge current (waveform 8/20µs) to pass once, and allow the nominal discharge current (waveform 8/20µs) to pass 15 times to characterize the ability of the lightning arrester to discharge the lightning current. When choosing a lightning arrester, we must pay attention to the difference between the maximum discharge current and the nominal discharge current. Most lightning arrester manufacturers name their lightning arrester models based on the maximum discharge current. Many users of surge protectors do not notice the difference between the maximum discharge current and the nominal discharge current when choosing. Some users even regard the maximum discharge current as the most important basis for the selection of surge protectors, while ignoring the nominal discharge current. In fact, the national standard clearly stipulates that the nominal discharge current must be the main basis for selecting lightning protection devices. For lightning protection product models named after the maximum discharge current, it is necessary to check whether the nominal discharge current parameters meet the corresponding national standard requirements.
Different electrical grounding systems should use different surge protectors, and this is often overlooked by non-professional lightning protection users. The impact of different grounding systems on the selection of surge protectors can be divided into two aspects:The maximum continuous working voltage of the lightning arrester and the structural form of the lightning arrester. The maximum continuous working voltage refers to the maximum AC voltage rms or DC voltage that is allowed to be permanently applied to the lightning arrester, and its value is equal to the rated voltage. When the voltage applied to the lightning protection device is greater than the maximum continuous working voltage it can withstand, the lightning protection device will be damaged. If the maximum continuous working voltage is selected higher, the surge protector is not easy to be damaged when the voltage is unstable, but the residual voltage of the surge protector will be increased.
Due to the irregularity of the current lightning protection industry, many lightning protection manufacturers have not tested this project for their lightning protection devices, and this indicator is very important to the safety of lightning protection devices. It is one of the main indicators to measure the performance of lightning protection products. First, it needs to attract enough attention from customers.
The failure form of the voltage-limiting lightning arrester is a short circuit. When the lightning arrester with poor quality fails, it may catch fire and cause serious accidents. The national standard on the transient overvoltage characteristics of the lightning arrester is formulated to ensure that the lightning arrester will not cause fire and other safety accidents when it fails.
The transient overvoltage characteristic index requires the surge protector to apply a certain value of overvoltage (depending on the system), the duration is 200ms, and the test current is limited to 300A (effective value), the thin paper covered on the periphery of the surge protector during the test Or gauze cannot burn and catch fire. At the same time, when the power frequency voltage equal to the maximum continuous working voltage is applied for 1min, and the current does not exceed the effective value of 0.5mA, the tripping structure of the arrester will operate, and there should be an obvious, effective and permanent disconnection mark on the arrester.
The surge protection device is live after installation, so the national standard puts forward requirements for preventing direct contact, that is, when the surge protection device is installed and wired in normal use, the live parts should not be easy to touch. The lightning protectors currently on the market, including some well-known foreign brand lightning protectors, may also have defects in this indicator, and users should pay attention to them when choosing.
Gigabit Ethernet Surge Protector: Safeguarding the Stable Operation of Smart Cities and Digital Monitoring SystemsApril 23, 2025As society continues to develop, smart cities and intelligent buildings are emerging everywhere like mushrooms after rain. We can see various digital network cameras standing on street corners, quietl...view
Characteristics and applications of combination type surge protectorsMarch 25, 2024Combination type surge protection devices (SPDs) are advanced surge protection systems designed to provide enhanced protection against transient overvoltages and surges in electrical systems. They typ...view
Protecting Your Business Investments: The Role of Power Surge MonitoringSeptember 11, 2023In today's business landscape, where technology plays a central role in operations, safeguarding your electronic assets is paramount. Power surges, those sudden, unpredictable spikes in electrical...view
Understanding the Function and Installation Method of Surge Protection BoxJuly 3, 2024As computer networks become increasingly integrated into people's lives and work, heralding the advent of the digital and information era, the importance of data center rooms and lightning protect...view
The Surge Protector Will Be Effective 100%?November 28, 2023No surge protector can provide 100% protection against all possible electrical surges or power-related issues. Surge protectors are designed to limit the voltage supplied to an electrical device by ei...view
Understanding the Hazards of Ground Potential Rise BackflashAugust 11, 2025Ground Potential Rise (GPR) backflash refers to the phenomenon where, during a lightning strike or other strong electrical interference event, the lightning current or overvoltage is discharged throug...view