Signal surge protector (SPD) can be divided into telephone signal surge protector, network signal surge protector, control signal surge protector, high-power broadcast signal surge protector, and monitoring signal surge protector according to the different protected lines. Surge protector, video signal surge protector, etc. Today, Techwin will share with you the "Structure and Circuit Design of Signal Surge Protector".
The telephone line is a symmetrical double line, which can also be regarded as a parallel line. Its working power supply has a DC voltage of 48V, a voltage of 90V during ringing, and an operating frequency of 64kbits/s. Therefore, the surge protector used on this line should be The DC operating voltage is greater than 190V but less than 260V, and the impulse breakdown voltage is less than 700V. Therefore, it is generally required that the surge protector can also withstand a lightning strike voltage of 4kV and a lightning strike current of more than 5kA.
RS232 communication lines are generally divided into several types: one is the direct connection of the 25-pin cable line; the other is the direct connection of the twisted pair; the other is to add a modem at both ends of the twisted pair, and then convert it into a 25-pin cable. . There are also RS232 boards with 15-pin and 9-pin connectors. Different protection modes can be used for different communication line modes. Since the working voltage of the RS232 interface is below 15V and the transmission rate is hundreds of kbits/s, the insertion loss within the working frequency range is not greater than 1dB, so the parameter selection of the RS232 industrial surge protector should be determined when the DC clamping voltage is not Less than 15V, the impulse clamping voltage is not more than 26V, the transmission rate is not less than 1Mkbits/s, the withstand voltage is not less than 1.5kV, and the lightning current capacity is not less than 3kA.
The RS485 communication line has a 9-pin cable line connection method, but more is a twisted pair connection method. For different communication line methods, different protection modes can be used. Since the operating voltage of the RS485 interface is below 12V, the transmission rate is 100kbits/s, and the insertion loss within the operating frequency range is not greater than 1dB, so for the parameters of the RS485 interface surge protector module: DC clamping voltage not less than 12V, impulse clamping voltage It is not more than 22V, the transmission rate is not less than 1Mkbits/s, the withstand voltage is not less than 1.5kV, and the lightning current capability is not less than 3kA.
The 2Mkbits/s interface line types of E1 include twisted pair type, coaxial type and RJ45 network cable type, but in essence they all have one loop for receiving and sending. The signal level of the E1 dedicated line is generally not greater than 3V, and the transmission rate is 2047kbits/s. Therefore, the parameter selection of the surge protector of the E1 interface should be determined when the DC clamping voltage is not greater than 5V, the impulse clamping voltage is not greater than 20V, and the transmission The rate is not less than 2Mkbits/s, the insertion loss is not more than 1dB in the operating frequency range, the withstand voltage is not less than 1.5kV, and the lightning current resistance capability is not less than 5kA.
Ordinary coaxial interface surge protector, such as BNC interface type, has two circuits, one is to use the outer skin as the ground, and only consider the protection of the core wire to the outer skin; the other is that the outer skin is not directly grounded, the surge protector In addition to considering the protection of the core wire to the outer skin, the module also has the protection of the outer skin to the ground. Since the lightning impulse energy on the communication line is not very large, this kind of surge protector does not require high lightning current capability. Generally, the lightning resistance current of 10kA is enough. However, due to the high communication frequency band, the requirements for attenuation and standing wave ratio are relatively high. , it is generally required that the insertion loss of the working frequency band is not greater than 0.2dB, and the standing wave ratio is not greater than 1.1.
Protecting Your Business Investments: The Role of Power Surge MonitoringSeptember 11, 2023In today's business landscape, where technology plays a central role in operations, safeguarding your electronic assets is paramount. Power surges, those sudden, unpredictable spikes in electrical...view
Harm of lightning to DCS system of nuclear power plant and key points of lightning protection designJuly 8, 2022Lightning is a kind of meteorological disaster that often occurs in most areas of our country. It has the characteristics of strong suddenness and great harm, and often brings very serious threats to ...view
Surge Protector: Guardian of Thunderstorm WeatherMarch 13, 2023During the high-frequency thunderstorm season, the unstable weather brings not only inconvenience to people's travel but also poses potential safety hazards. Lightning waves can be introduced with...view
Surge Protector Grading Protection-Do You Know It?March 13, 2023The surge current energy generated by lightning strikes is enormous, so a step-by-step release approach should be adopted to release the surge current into the ground in stages.1. Graded Protection of...view
The role of ground potential counterattack protectorSeptember 28, 2021When the power distribution system is struck by lightning and when switching on or off inductive loads or large loads, it often produces high operating overvoltages, also called surge voltages. Surges...view
Guide to the Function and Selection of Surge Protection Device for LightningMarch 18, 2025As lightning hazards pose increasing threats to buildings and electronic devices, Surge Protection Device for Lightning has become particularly important in modern buildings and power systems. This ar...view